8 Outlets Lighting Relay Controller
8 Outlets Lighting Relay Controller
  • 8 Outlets Lighting Relay Controller
  • 8 Outlets Lighting Relay Controller

8 Outlets Lighting Relay Controller

Features of the Light Controller.

• Controls up to four or eight 1000W high intensity discharge (HID) ballasts, including both metal halide (MH) and high pressure sodium (HPS) lighting systems.

• Integrated 120V trigger cable facilitates any timed lighting sequence when connected to a standard 24-hour timing device or other environmental controller (available separately).

• Green LED indicator illuminates when light controller. is activated and ON via the trigger cable function.

• Composed of high-quality components for reliable, long-term performance.

• Wall-mountable.

Description

 

Specifications

4 Outlets Light Controller

8 Outlets Light Controller

Main Power Voltage: 120V OR 240V

Main Power Voltage: 120V OR 240V

Receptacle Type: 4 Universal Outlets

Receptacle Type: 8 Universal Outlets

Max Lighting Wattage: 4000W total/1000W per Outlet

Max Lighting Wattage: 8000W total/1000W per Outlet

Max Relay Amperage: 30A

Max Relay Amperage: 30A (x2Relays)

Trigger Cable Voltage: 120V

Trigger Cable Voltage: 120V

Operating Temperature Range: 32-110°F

Operating Temperature Range: 32-110°F

Operating Humidity Range: 0-99% RH Noncondensing

Operating Humidity Range: 0-99% RH Noncondensing

Minimum Relay Operations: 100,000 @ Full Load

Minimum Relay Operations: 100,000 @ Full Load

 

IMPORTANT PRECAUTIONS

• Consult a licensed electrician prior to installation or have the unit professionally installed.

• Read all product specifications and instructions before installation and operation.

• DO NOT install the Light Controller if you are unfamiliar with electrical wiring and circuits OR if you do not fully understand the instructions.

• All local and national electrical codes MUST be followed.

• Use the Light Controller ONLY for its intended purpose.

• DO NOT exceed the maximum ratings of this unit.

• Verify all devices to be controlled by the Light Controller are of the correct voltage.

• Unit is for indoor use only. Exercise extreme caution in moist or humid environments.

• Improper installation or use of this controller could result in severe damage and/or personal injury.

Main Power Requirements

A main power source must be supplied for the lights to function.

• Verify main power source has the same voltage and amperage ratings as the equipment being controlled by the Light Controller (see specifications above).

• Main power can be hardwired to a circuit breaker panel or installed using the appropriate high-amperage portable cable and connector end (not included).

• 4 Outlets Light Controller, Use only a 30A, 2-pole circuit breaker and #10 AWG wire to provide the main power.

• 8 Outlets Light Controller, Use only a 50A, 2-pole circuit breaker and #6 AWG wire to provide the main power.

• Proper connection of the ground wire to the ground lug is critical for safe operation.

• All connected ballasts MUST BE wired correctly and according to the main power voltage. 

  *The Light Controller with universal 120/240V receptacles can be used to operate 120V devices ONLY IF the main power is also wired in at 120V. Connecting a 120V ballast to a controller with 240V main power could result in damage or fire. Consult the ballast manufacturer for any questions concerning the electrical requirements.

* 240V main power requires ballasts wired for 240V (most common application).

  * 120V main power requires ballasts wired for 120V.

Installation

DO NOT connect ballasts to the Light Controller until AFTER the main power has been properly installed.

Main Power Connection

• Use a screwdriver to remove each of the four screws securing the front cover to the back casing.

• Feed the properly rated main power cable into the cable clamp and tighten the clamp to secure the cable in place.

• Insert the green or bare ground wire into the grounding terminal and secure.

• Strip the insulation from the main power wires. Insert and tighten each bare wire end into the 2 power connection points on the power relay (L1 and L2 shown above picture). Secure the wires tightly to ensure a good connection. Loose connections will cause the terminals on the relay to overheat which can cause damage to the unit that is NOT covered by the warranty.

• Turn on the circuit breaker or connect the main power cable connection. The Light Controller will now be powered.

• Use a voltage meter to verify correct voltage BEFORE plugging ballasts into the Light Controller. If connected to a 240V circuit, the voltage meter should read approximately 240V. If connected to a 120V circuit, the voltage meter should read approximately 120V.

• Once all voltage has been verified, carefully reinstall the front cover.

Trigger Cable Testing

• 120V trigger cable MUST be connected to an external timing device or controller providing 120V to the main relay.

• Main relay will close when the trigger cable is connected and activated, producing a distinct click.

• When the trigger cable is plugged in to an external device and the externally connected timer/controller is ON, the green LED indicator light will illuminate.

• When the trigger cable is disconnected from the external timer/controller, the green LED indicator light will turn off.

• Unplug the trigger cable from the external timer/controller after it has been tested for proper operation.

Ballast Connection

• Verify trigger cable is disconnected from the external timer or controller.

• Connect ballast power cables to the receptacles on the Light Controller.

• Connect the trigger cable to the external timer or controller.